ACM8/CB Sub-Assembly - 5 -
LED Diagnostics:
ACM8 & ACM8CB Access Power Controller
LED ON OFF
LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized.
Trg(Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Terminal Identification Tables:
ACM8 & ACM8CB Access Power Controller
Terminal Legend Function/Description
-- Power + 12VDCor24VDCinputfrompowersupplyboard.
-- Control +
These terminals can be connected to a separate, UL Listed power supply to
provide isolated operating power for the ACM8/ACM8CB
(jumpersJ1andJ2mustberemoved).
TRIGGER
INPUT 1 - INPUT 8
IN,GND
From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit pir’s, etc.).
OUTPUT 1-OUTPUT 8
NC, C, NO, COM
12to24voltsAC/DCtriggercontrolledoutputs:
Fail-Safe [NC positive (+) & COM Negative (-)],
Fail-Secure [NO positive (+) & COM Negative (-)],
Auxiliary output [C positive (+) & COM Negative (-)]
(WhenusingACpowersuppliespolarityneednotbeobserved),
NC,C,NObecomeform“C”5amp24VAC/VDCrateddryoutputswhenfusesare
removed (ACM8). Contacts shown in a non-triggered state.
FACP INTERFACE
T, + INPUT -
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (Fig. 3 through 7, pg. 6).
FACP INTERFACE
NC, C, NO
Form“C”relaycontactrated@1amp28VDCforalarmreporting.
(This output has not been evaluated by UL).