Overview:
T
hese units convert one (1) 12 to 24 volt AC or DC input into eight (8) independently controlled fused or PTC protected
o
utputs. These power outputs can be converted to dry form “C” contacts (ACM8 & ACM8E only). Outputs are activated
b
y an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad,
Push Button, PIR, etc. The units will route power to a variety of access control hardware devices including Mag Locks,
Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. Units are
designed to be powered by one common power source which will provide power for both the board operation and locking
devices, or two (2) totally independent power sources, one (1) providing power for board operation and the other for lock
/ accessory power. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other aux-
iliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
ACM8 & ACM8CB Series Configuration Reference Chart:
ACM8 x - 3.5 amp *
ACM8CB - x 2.5 amp x
ACM8E x - 3.5 amp x *
ACM8CBE - x 2.5 amp x x
*When used with Class 2 Rated Power Limited power supply.
Specifications:
12 to 24volt AC or DC operation (setting not required).
(.6 amp @ 12volt, .3 amp @ 24volt current consumption with all relays energized).
Power supply input options:
a) One (1) common power input (board and lock power).
b) Two (2) isolated power inputs (one (1) for board power and one (1) for lock/hardware power).
Eight (8) Access Control System trigger inputs:
a)
Eight (8) normall
y open (NO) inputs.
b) Eight (8) open collector sink inputs.
c) Any combination of the above.
Eight (8) independentl
y controlled outputs:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b)
Eight (8) dr
y form “C” 5 amp rated relay outputs (ACM8 & ACM8E only).
c)
An
y combination of the abo
v
e (ACM8 & ACM8E only).
Eight (8) auxiliary power outputs (unswitched).
Output ratings:
- Fuses are rated 3.5 amp each.
- PTCs are rated 2.5 amp each.
Main fuse is rated at 10 amp.
Note: T
otal output cur
rent is determined by the power supply, not to exceed a maximum of 10 amp total.
Red LEDs indicate outputs are triggered (relays energized).
Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b)
P
olarity re
v
ersal input from F
ACP signaling circuit.
FACP output relay (form “C” contact rated @ 1 amp 28VDC not evaluated by UL).
Green LED indicates when FACP disconnect is triggered.
Removable terminal blocks facilitate ease of installation.
Board Dimensions (appro
ximate): 8”L x 4.5”W x 1.25”H (A
CM8 and
A
CM8CB)
Enclosure Dimentions: 15.5”H x 12”W x 4.5”D (ACM8E and ACM8CBE)
Altronix
Model Number
Fuse Protected
Outputs
PTC Protected
Outputs
Output Ratings
Agency Listings
UL Listings and
File Numbers
Enclosure
Class 2 Rated
Power Limited
- 2 -
UL File # BP6714
UL Listed for Access Control
System Units (UL 294).
“Signal Equipment” Evaluated to
CSA Standard C22.2
No.205-M1983