
AL1024ULACM converts a 115VAC 60Hz input into eight (8) independently con-
trolled 24VDC Fail-Safe and/or Fail-Secure outputs with a total of 10 amp continuous
supply current. Outputs are activated by an open collector sink or normally open (NO)
dry trigger input from an Access Control System, Card Reader, Keypad, Push Button,
PIR, etc. This unit will route power to a variety of access control hardware devices
including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The outputs will
operate in both Fail-Safe and/or Fail-Secure modes. This unit is designed to be pow-
ered by one common power source (factory installed) which will provide power for
both the board operation and locking devices, or two (2) totally independent power
sources, one (1) providing power for board operation and the other for lock / acces-
sory power. The FACP Interface enables Emergency Egress, Alarm Monitoring, or
may be used to trigger other auxiliary devices. The fire alarm disconnect feature is
individually selectable for any or all of the eight (8) outputs.
AL1024ULACM
Power Supply/Chargers w/Multi-Output
Access Power Controllers Rev. DSAL1024ULACM_01032013
Overview
Specifications
AL1024ULACM
Input:
• Input115VAC60Hzrated@4.4amp.
• Powersupplyinputoptions:
a) One (1) common power input for ACM8/
ACM8CB and lock power (factory installed).
b)Two (2) isolated power inputs - One (1) to power
the ACM8/ACM8CB and one (1) for lock
accessory power, (external power supply
is required). (Current is determined by the
power supply connected, not to exceed a
maximum of 10 amp total).
• Eight(8)AccessControlSystemtriggerinputs.
Inputoptions:
a) Eight (8) normally open (NO) inputs.
b)Eight (8) open collector inputs.
c) Any combination of the above.
Output:
• 24VDC@10ampsupplycurrent.
• Eight(8)independentlycontrolledoutputs.
Outputoptions:
a) Eight (8) Fail-Safe and/or Fail-Secure
power outputs.
• Eight(8)auxiliarypoweroutputs(unswitched)
• Outputratings:
-Fusesarerated@3.5amp.
• Filteredandelectronicallyregulatedoutputs
(built-in power supply).
Features:
• FireAlarmdisconnect(latchingornon-latching)is
individually selectable for any or all of the
eight (8) outputs.
Features (cont’d):
• FireAlarmdisconnectinputoptions:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b)Polarity reversal input from FACP signaling circuit.
• AlarmoutputrelayindicatesthatFACPinputis
triggered(form“C”contactrated@1amp28VDC
not evaluated by UL).
• Shortcircuitandthermaloverloadprotection.
Visual Indicators:
• RedLEDsindicateoutputsaretriggered
(relays energized).
• GreenLEDindicatesFACPdisconnectistriggered.
• ACinputandDCoutputLEDindicators.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• AL1024ULXB(PowerSupplyBoard)
maximum charge current 3.6 amp.
• Automaticswitchovertostand-bybatterywhenACfails.
• Zerovoltagedropwhenunitswitchesovertobattery
backup (AC failure condition).
• ACfailsupervision(form“C”contact).
• Batteryfailandbatterypresencesupervision
(form “C” contact).
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• ACM8boardmainfuseisratedat10amp.
• BTU/Hr.:122.84BTU/Hr.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
115.5”(393.7mm)x12”(304.8mm)x4.5”(114.3mm)
- Accommodates up to two (2) 12AH batteries.
• Productweight(approx.):11.75 lbs. (5.33 kg).
• Shippingweight(approx.):13.05lbs.(5.92kg).
Comentarios a estos manuales