Power Supply/ChargersInstallation GuideModels Include:eFlow104N/eFlow104NX- 10 amp @ 24VDCeFlow104N8/ eFlow104N8D/eFlow104NX8 eFlow104NX8D- 10 amp @ 2
- 10 - eFlow104N SeriesNEC Power-Limited Wiring Requirements for eFlow104NX Models:Power-limited and non power-limited circuit wiring must remain sep
eFlow104N Series - 11 -Enclosure Dimensions (BC300) (approximate H x W x D):eFlow104N, eFlow104N8, eFlow104N8D, eFlow104N16, eFlow104N16D13.5” x 13”
- 12 - eFlow104N Series1.5”(38.1mm)1.5”(38.1mm)1.5”(38.1mm)5.0”(127.0mm)5.0”(127.0mm)1.5”(38.1mm)2.0”(50.8mm)2.0”(50.8mm)1.75”(44.45mm)1.75”(44.45mm)
eFlow104N Series - 13 -Appendix A - UL Listed Compatible DevicesA.1 Four (4) Wire Smoke DetectorsTable A-1 below lists four (4) wire smoke detectors
- 14 - eFlow104N SeriesNotes:
eFlow104N Series - 15 -Notes:Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.1
CUT ALONG DOTTED LINEPower Supply/Chargers Operating GuideModels Include:ModelInput120VAC, 60HzOutputAuxiliary Power-LimitedOutput (unswitched)RippleV
- 2 - eFlow104N SeriesOverview:The eFlow104N power supply/chargers convert a 120VAC / 60Hz input to a 24VDC nominal output(see Power Supply Configura
eFlow104N Series - 3 -Specifications:Installation Instructions:Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA
- 4 - eFlow104N Series9. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [
eFlow104N Series - 5 -Terminal Identification:Power Distribution ModuleTerminal LegendPD8UL/PD8ULCBTerminal LegendPD16W/PD16WCBFunction/Description1
- 6 - eFlow104N SeriesPower Distribution Module(s):Fig. 3a - PD8UL Power Distribution Board Fig. 3b - PD8ULCB - Power Distribution Board Power-Limi
eFlow104N Series - 7 -LGNNCCNONCCNOBAT FAILAC FAIL--- DC +ACAC1DC--- BAT +– AUX +TRIGGER EOLSUPERVISED5A 250VRESETGND NOdisableenable2 hr
- 8 - eFlow104N SeriesNEC Power-Limited Wiring Requirements for eFlow104N Models:Power-limited and non power-limited circuit wiring must remain separ
eFlow104N Series - 9 -DoorWire Strap(fromEnclosureto Door)Battery & AC SupervisionCircuit (power-limited)LGNNCCNONCCNOBAT FAILAC FAIL--- DC +A